Kode
Error AC York
York Minisplits
Perlawanan Sensor Suhu Bacaan
Suhu = 0C
Ohms K = 35K
Suhu = 10C
Ohms K = 20K
Suhu = 20C
Ohms K = 13K
Suhu = 30C
Ohms K = 8K
Kesalahan Kode untuk Model RAHC, YKHC & YUHC
Indoor lampu
Operasi = flash
Timer = flash
Defrost = flash
Kesalahan Soal = Terbuka
Operasi =
Timer =
Defrost = flash
Kesalahan = ID Sensor Air Gagal
Operasi = flash
Timer =
Pencairan =
Kesalahan = Sensor Pipa ID Gagal
Operasi =
Timer =
Defrost = flash
Kesalahan = OD Sensor Pipa Gagal
Operasi = flash
Timer = flash
Pencairan =
Kesalahan = PCB Gagal
Di luar ruangan LED 3ph hanya model
LED flash 1 =
LED 2 = Off
LED 3 = Off
Kesalahan = Tahap Kesalahan
LED flash 1 =
LED flash 2 =
LED 3 = Off
Kesalahan = Tekanan Beralih
LED 1 = Off
LED 2 = Off
LED flash 3 =
Kesalahan = Arus berlebihan
LED 1 = Off
LED flash 2 =
LED flash 3 =
Kesalahan = OD Pipe Sensor
LED 1 = Off
LED flash 2 =
LED 3 = Off
Kesalahan = OD Air Sensor
LED flash 1 =
LED flash 2 =
LED flash 3 =
Kesalahan = Hi Temp Perlindungan
HVHC Inverter Kesalahan Codes
Tampilan Indoor = E0
ID PCB Gagal
Terbuka LCD
1 = On
2 Merah = Off
3 Green = Off
4 Kuning = Off
Terhubung ke Daya
Indoor Tampilan = E1
Comms Gagal
Terbuka LCD
1 = Off
2 Merah = Off
3 Green = Off
4 Kuning = Off
Power atau OD PCB Fail
Indoor Tampilan = E3
Daya Abnormal
Terbuka LCD
1 = On
2 Merah = On
3 Green = Off
4 Kuning = Off
Comms Gagal
Indoor Tampilan = E4
OD Sensor Gagal
Terbuka LCD
1 = On
2 Merah = Off
3 Green = Off
4 Kuning = On
Compressor Overcurrent
Indoor Tampilan = E5
Sensor ID Gagal
Terbuka LCD
1 = On
2 Merah = Off
3 Green = flash
4 Kuning = flash
OD Sensor Air Gagal E5
Tampilan Indoor = E6
Inverter Modul
Terbuka LCD
1 = On
2 Merah = flash
3 Green = Off
4 Kuning = flash
OD Sensor Pipa Fail E5
Indoor Tampilan = PO
IPM Perlindungan
Terbuka LCD
1 = On
2 Merah = On
3 Green = flash
4 Kuning = On
OD Power Supply P1
Indoor Tampilan = P1
OD Power Supply
Terbuka LCD
1 = On
2 Merah = Off
3 Hijau = On
4 Kuning = Off
IPM Perlindungan P0
Indoor Tampilan = P2
Compressor Hi Temp
Terbuka LCD
1 = On
2 Merah = Off
3 Hijau = On
4 Kuning = On
Compressor Temp P2
Tampilan Indoor = P3
Luar Rendah Temp
Terbuka LCD
1 = On
2 Merah = On
3 Green = Off
4 Kuning = Off
Comms E1
Indoor Tampilan = P4
Inverter / Kompresor Gagal
Terbuka LCD
1 = On
2 Merah = On
3 Green = flash
4 Kuning = flash
Inv / Comp Fail P4
Model SM-YJCC-YJHC
Produk yang akan diperiksa terlebih dahulu
1. Apakah tegangan listrik yang benar? Tegangan input harus tegangan Peringkat 10%. Pendingin udara tidak dapat beroperasi dengan baik jika tegangan keluar dari kisaran ini.
2. Apakah kabel link yang menghubungkan unit indoor dan unit outdoor dihubungkan dengan benar? Silakan mengacu ke "diagram pengkabelan" Periksa terminal jika unit indoor dan unit outdoor dengan benar dihubungkan dengan jumlah yang sama dari kabel.
3. Ketika terjadi masalah karena isi digambarkan dalam tabel di bawah ini, itu adalah gejala tidak berhubungan dengan themalfunction dari AC.
Pengoperasian AC = Dalam mode operasi COOL, kompresor tidak beroperasi pada suhu kamar lebih tinggi daripada suhu pengaturan bahwa fan dalam ruangan harus operate.In mode operasi HEAT, kompresor tidak beroperasi pada suhu kamar lebih rendah dari pengaturan suhu yang fan dalam ruangan harus beroperasi.
Penjelasan = Ini terjadi setelah penundaan 3 menit ketika kompresor reoperated. Fenomena yang sama terjadi ketika listrik adalah on.As fenomena bahwa kompresor reoperated setelah adelay dari 3 menit, kipas ruangan diatur secara otomatis withreference ke suhu pukulan udara.
Pengoperasian AC = Fan pengaturan kecepatan tidak diperbolehkan dalam mode AUTO atau KERING
Penjelasan = kecepatan kipas dalam ruangan diatur ke rendah dalam kecepatan mode.Fan DRY dari 3 langkah akan dipilih secara otomatis dalam mode AUTO.
Pengoperasian AC = Compressor berhenti beroperasi sebentar-sebentar dalam mode KERING.
Penjelasan = Kompresor operasi secara otomatis dikontrol dalam modedepending DRY pada suhu kamar dan kelembaban.
Pengoperasian AC = Compressor dari unit outdoor beroperasi meskipun dimatikan dalam mode HEAT.
Penjelasan = Bila unit dimatikan sementara de-es diaktifkan, thecompressor terus beroperasi hingga 10 menit (maksimum) sampai deice selesai.
Pengoperasian AC = Timer lampu lampu indikator dan doesnot AC beroperasi.
Penjelasan = Timer sedang diaktifkan dan unit dalam satuan mode.The siap beroperasi secara normal jika operasi timer dibatalkan
Pengoperasian AC = The kompresor dan kipas dalam ruangan berhenti sebentar-sebentar di HEATmode.
Penjelasan = Kompresor dan kipas berhenti sebentar-sebentar dalam ruangan jika suhu ruangan melebihi suhu pengaturan untuk melindungi wilayah kompresor dari udara panas dalam mode HEAT
Pengoperasian AC = fan Indoor dan kipas berhenti sebentar-sebentar di luar ruangan dalam mode HEAT.
Penjelasan = Kompresor beroperasi dalam siklus terbalik untuk menghapus exteriorice dalam mode HEAT, dan kipas indoor dan kipas luar tidak beroperasi sebentar-sebentar untuk dalam 20% dari operasi total panas
Pengoperasian AC = kompresor berhenti sebentar-sebentar dalam mode COOL atau DRYmode, dan kecepatan kipas dari unit indoor menurun
Penjelasan = kompresor berhenti sebentar-sebentar atau kecepatan kipas unit indoor menurun untuk mencegah dalam / luar udara frozendepending pada suhu udara di dalam / luar.
SELF DIAGNOSA FUNGSI
Perusahaan kami menyediakan pengguna akhir dengan layanan bijaksana dengan memasang berbagai sistem diagnostik untuk menunjukkan kinerja yang tidak teratur berikut
Checkcode = FAULT F6
Diagnosis kerusakan = PG bermotor kesalahan
Checkcode = FAULT F7
Diagnosis kerusakan = kesalahan sensor TEMP Indoor
Checkcode = F8 FAULT
Diagnosisofmalfunction = Indoor kumparan kesalahan TEMP sensor pipa
Checkcode = FAULT F9
Diagnosisofmalfunction = Terbuka kumparan kesalahan TEMP sensor pipa
York Minisplits
Perlawanan Sensor Suhu Bacaan
Suhu = 0C
Ohms K = 35K
Suhu = 10C
Ohms K = 20K
Suhu = 20C
Ohms K = 13K
Suhu = 30C
Ohms K = 8K
Kesalahan Kode untuk Model RAHC, YKHC & YUHC
Indoor lampu
Operasi = flash
Timer = flash
Defrost = flash
Kesalahan Soal = Terbuka
Operasi =
Timer =
Defrost = flash
Kesalahan = ID Sensor Air Gagal
Operasi = flash
Timer =
Pencairan =
Kesalahan = Sensor Pipa ID Gagal
Operasi =
Timer =
Defrost = flash
Kesalahan = OD Sensor Pipa Gagal
Operasi = flash
Timer = flash
Pencairan =
Kesalahan = PCB Gagal
Di luar ruangan LED 3ph hanya model
LED flash 1 =
LED 2 = Off
LED 3 = Off
Kesalahan = Tahap Kesalahan
LED flash 1 =
LED flash 2 =
LED 3 = Off
Kesalahan = Tekanan Beralih
LED 1 = Off
LED 2 = Off
LED flash 3 =
Kesalahan = Arus berlebihan
LED 1 = Off
LED flash 2 =
LED flash 3 =
Kesalahan = OD Pipe Sensor
LED 1 = Off
LED flash 2 =
LED 3 = Off
Kesalahan = OD Air Sensor
LED flash 1 =
LED flash 2 =
LED flash 3 =
Kesalahan = Hi Temp Perlindungan
HVHC Inverter Kesalahan Codes
Tampilan Indoor = E0
ID PCB Gagal
Terbuka LCD
1 = On
2 Merah = Off
3 Green = Off
4 Kuning = Off
Terhubung ke Daya
Indoor Tampilan = E1
Comms Gagal
Terbuka LCD
1 = Off
2 Merah = Off
3 Green = Off
4 Kuning = Off
Power atau OD PCB Fail
Indoor Tampilan = E3
Daya Abnormal
Terbuka LCD
1 = On
2 Merah = On
3 Green = Off
4 Kuning = Off
Comms Gagal
Indoor Tampilan = E4
OD Sensor Gagal
Terbuka LCD
1 = On
2 Merah = Off
3 Green = Off
4 Kuning = On
Compressor Overcurrent
Indoor Tampilan = E5
Sensor ID Gagal
Terbuka LCD
1 = On
2 Merah = Off
3 Green = flash
4 Kuning = flash
OD Sensor Air Gagal E5
Tampilan Indoor = E6
Inverter Modul
Terbuka LCD
1 = On
2 Merah = flash
3 Green = Off
4 Kuning = flash
OD Sensor Pipa Fail E5
Indoor Tampilan = PO
IPM Perlindungan
Terbuka LCD
1 = On
2 Merah = On
3 Green = flash
4 Kuning = On
OD Power Supply P1
Indoor Tampilan = P1
OD Power Supply
Terbuka LCD
1 = On
2 Merah = Off
3 Hijau = On
4 Kuning = Off
IPM Perlindungan P0
Indoor Tampilan = P2
Compressor Hi Temp
Terbuka LCD
1 = On
2 Merah = Off
3 Hijau = On
4 Kuning = On
Compressor Temp P2
Tampilan Indoor = P3
Luar Rendah Temp
Terbuka LCD
1 = On
2 Merah = On
3 Green = Off
4 Kuning = Off
Comms E1
Indoor Tampilan = P4
Inverter / Kompresor Gagal
Terbuka LCD
1 = On
2 Merah = On
3 Green = flash
4 Kuning = flash
Inv / Comp Fail P4
Model SM-YJCC-YJHC
Produk yang akan diperiksa terlebih dahulu
1. Apakah tegangan listrik yang benar? Tegangan input harus tegangan Peringkat 10%. Pendingin udara tidak dapat beroperasi dengan baik jika tegangan keluar dari kisaran ini.
2. Apakah kabel link yang menghubungkan unit indoor dan unit outdoor dihubungkan dengan benar? Silakan mengacu ke "diagram pengkabelan" Periksa terminal jika unit indoor dan unit outdoor dengan benar dihubungkan dengan jumlah yang sama dari kabel.
3. Ketika terjadi masalah karena isi digambarkan dalam tabel di bawah ini, itu adalah gejala tidak berhubungan dengan themalfunction dari AC.
Pengoperasian AC = Dalam mode operasi COOL, kompresor tidak beroperasi pada suhu kamar lebih tinggi daripada suhu pengaturan bahwa fan dalam ruangan harus operate.In mode operasi HEAT, kompresor tidak beroperasi pada suhu kamar lebih rendah dari pengaturan suhu yang fan dalam ruangan harus beroperasi.
Penjelasan = Ini terjadi setelah penundaan 3 menit ketika kompresor reoperated. Fenomena yang sama terjadi ketika listrik adalah on.As fenomena bahwa kompresor reoperated setelah adelay dari 3 menit, kipas ruangan diatur secara otomatis withreference ke suhu pukulan udara.
Pengoperasian AC = Fan pengaturan kecepatan tidak diperbolehkan dalam mode AUTO atau KERING
Penjelasan = kecepatan kipas dalam ruangan diatur ke rendah dalam kecepatan mode.Fan DRY dari 3 langkah akan dipilih secara otomatis dalam mode AUTO.
Pengoperasian AC = Compressor berhenti beroperasi sebentar-sebentar dalam mode KERING.
Penjelasan = Kompresor operasi secara otomatis dikontrol dalam modedepending DRY pada suhu kamar dan kelembaban.
Pengoperasian AC = Compressor dari unit outdoor beroperasi meskipun dimatikan dalam mode HEAT.
Penjelasan = Bila unit dimatikan sementara de-es diaktifkan, thecompressor terus beroperasi hingga 10 menit (maksimum) sampai deice selesai.
Pengoperasian AC = Timer lampu lampu indikator dan doesnot AC beroperasi.
Penjelasan = Timer sedang diaktifkan dan unit dalam satuan mode.The siap beroperasi secara normal jika operasi timer dibatalkan
Pengoperasian AC = The kompresor dan kipas dalam ruangan berhenti sebentar-sebentar di HEATmode.
Penjelasan = Kompresor dan kipas berhenti sebentar-sebentar dalam ruangan jika suhu ruangan melebihi suhu pengaturan untuk melindungi wilayah kompresor dari udara panas dalam mode HEAT
Pengoperasian AC = fan Indoor dan kipas berhenti sebentar-sebentar di luar ruangan dalam mode HEAT.
Penjelasan = Kompresor beroperasi dalam siklus terbalik untuk menghapus exteriorice dalam mode HEAT, dan kipas indoor dan kipas luar tidak beroperasi sebentar-sebentar untuk dalam 20% dari operasi total panas
Pengoperasian AC = kompresor berhenti sebentar-sebentar dalam mode COOL atau DRYmode, dan kecepatan kipas dari unit indoor menurun
Penjelasan = kompresor berhenti sebentar-sebentar atau kecepatan kipas unit indoor menurun untuk mencegah dalam / luar udara frozendepending pada suhu udara di dalam / luar.
SELF DIAGNOSA FUNGSI
Perusahaan kami menyediakan pengguna akhir dengan layanan bijaksana dengan memasang berbagai sistem diagnostik untuk menunjukkan kinerja yang tidak teratur berikut
Checkcode = FAULT F6
Diagnosis kerusakan = PG bermotor kesalahan
Checkcode = FAULT F7
Diagnosis kerusakan = kesalahan sensor TEMP Indoor
Checkcode = F8 FAULT
Diagnosisofmalfunction = Indoor kumparan kesalahan TEMP sensor pipa
Checkcode = FAULT F9
Diagnosisofmalfunction = Terbuka kumparan kesalahan TEMP sensor pipa