Diagnosis display = H00
Abnormality
/ Protection control = No abnormality detected
Abnormality
Judgement =
Emergency
operation = Normal operation
Primary
location to verify =
Diagnosis
display = H11
Abnormality
/ Protection control = Indoor / Outdoor abnormal communication
Abnormality
Judgement = > 1 min after starting operation
Emergency
operation = Indoor fan operation only
Primary
location to verify = • Internal / external
cable connections • Indoor / Outdoor
PCB
Diagnosis
display = H14
Abnormality
/ Protection control = Indoor intake air temperature sensor abnormality
Abnormality
Judgement = Continue for 5 sec.
Emergency
operation =
Primary
location to verify = • Intake air
temperature sensor (detective or disconnected)
Diagnosis
display = H15
Abnormality
/ Protection control = Outdoor compressor temperature sensor abnormality
Abnormality
Judgement = Continue for 5 sec
Emergency
operation =
Primary
location to verify = Compressor temperature sensor (detective or
disconnected)
Diagnosis
display = H16
Abnormality
/ Protection control = Outdoor Current Transformer open circuit
Abnormality
Judgement =
Emergency
operation =
Primary
location to verify = • Outdoor PCB • IPM (Power
transistor) module
Diagnosis
display = H19
Abnormality
/ Protection control = Indoor fan motor mechanism locked
Abnormality
Judgement = 7 times occurance continuously
Emergency
operation =
Primary
location to verify = • Indoor PCB • Fan motor
Diagnosis
display = H23
Abnormality
/ Protection control = Indoor heat exchanger temperature sensor abnormality
Abnormality
Judgement =
Emergency
operation = O (Cooling only}
Primary
location to verify = • Heat exchanger
temperature sensor (detective or disconnected)
|
Diagnosis display = H24
Abnormality
/ Protection control = Indoor heat exchanger temperature sensor 2 abnormality
Abnormality
Judgement = Continue for 5 sec.
Emergency
operation =
Primary
location to verify = • Heat exchanger
temperature sensor (detective or disconnected)
Diagnosis
display = H27
Abnormality
/ Protection control = Outdoor intake air temperature sensor abnormality
Abnormality
Judgement = Continue for 5 sec.
Emergency
operation = O
Primary
location to verify = • Outdoor temperature
sensor (detective or disconnected)
Diagnosis
display = H28
Abnormality
/ Protection control = Outdoor heat exchanger temperature sensor abnormality
Abnormality
Judgement = Continue for 5 sec.
Emergency
operation = O
Primary
location to verify = • Outdoor heat
exchanger temperature sensor (detective or disconnected)
Diagnosis
display = H30
Abnormality
/ Protection control = Outdoor discharge air temperature sensor abnormality
Abnormality
Judgement = Continue for 5 sec.
Emergency
operation =
Primary
location to verify = • Outdoor temperature
sensor (detective or disconnected)
Diagnosis
display = H33
Abnormality
/ Protection control = Indoor / Outdoor wrong connection
Abnormality
Judgement =
Emergency
operation =
Primary
location to verify = • Indoor / Outdoor
supply voltage
Diagnosis
display = H38
Abnormality
/ Protection control = Indoor / Outdoor mismatch (brand code)
Abnormality
Judgement =
Emergency
operation =
Primary
location to verify =
Diagnosis
display = H50
Abnormality
/ Protection control = Ventilation motor abnormality
Abnormality
Judgement = 7 times occurance continuously
Emergency
operation =
Primary
location to verify = • Indoor PCB • Ventilation motor
|
Diagnosis display = H51
Abnormality
/ Protection control = Nozzle lock abnormality
Abnormality
Judgement = 2 times occurance continuously
Emergency
operation =
Primary
location to verify = •Nozzle
Diagnosis
display = H52
Abnormality
/ Protection control = Limit switch abnormality
Abnormality
Judgement =
Emergency
operation =
Primary
location to verify = • Indoor PCB
Diagnosis
display = H97
Abnormality
/ Protection control = Outdoor fan motor mechanism locked
Abnormality
Judgement = 2 times occurance within 30 minutes
Emergency
operation =
Primary
location to verify = • Indoor PCB • Fan motor
Diagnosis
display = H98
Abnormality
/ Protection control = Indoor high pressure protection
Abnormality
Judgement =
Emergency
operation =
Primary
location to verify = • Air filter dirty • Air circulation
short circuit
Diagnosis
display = H99
Abnormality
/ Protection control = Indoor heat exchanger anti-freezing protection
Abnormality
Judgement =
Emergency
operation =
Primary
location to verify = • Insufficient
refrigerant • Air filter dirty
Diagnosis
display = F11
Abnormality
/ Protection control = Cooling / Heating cycle changeover abnormality
Abnormality
Judgement = 4 times occurance within 30 minutes
Emergency
operation =
Primary
location to verify = •4-way valve • V-coil
Diagnosis
display = F90
Abnormality
/ Protection control = PFC control
Abnormality
Judgement = 4 times occurance within 10 minutes
Emergency
operation =
Primary
location to verify = • Voltage at PFC
|
Diagnosis display = F91
Abnormality
/ Protection control = Refrigerantion cycle abnormality
Abnormality
Judgement = 2 times occurance within 20 minutes
Emergency
operation =
Primary
location to verify = • No refrigerant
(3-way valve is closed)
Diagnosis
display = F93
Abnormality
/ Protection control = Compressor rotation failure
Abnormality
Judgement = 4 times occurance within 20 minutes
Emergency
operation =
Primary
location to verify = •Compressor
Diagnosis
display = F95
Abnormality
/ Protection control = Cool high pressure protection
Abnormality
Judgement = 4 times occurance within 20 minutes
Emergency
operation =
Primary
location to verify = • Outdoor refrigerant
circuit
Diagnosis
display = F96
Abnormality
/ Protection control = IPM (power transistor) overheating protection
Abnormality
Judgement = 4 times occurance within 30 minutes
Emergency
operation =
Primary
location to verify = • Excess refrigerant • Improper heat
radiation • IPM (Power transistor)
Diagnosis
display = F97
Abnormality
/ Protection control = Outdoor compressor overheating protection
Abnormality
Judgement = 4 times occurance within 10 minutes
Emergency
operation =
Primary
location to verify = • Insufficient
refrigerant • Compressor
Diagnosis
display = F98
Abnormality
/ Protection control = Total running current protection
Abnormality
Judgement = 3 times occurance within 20 minutes
Emergency
operation =
Primary
location to verify = • Excess refrigerant • Improper heat
radiation
Diagnosis
display = F99
Abnormality
/ Protection control = Outdoor Direct Current (DC) peak detection
Abnormality
Judgement = 7 times occurance continuously
Emergency
operation =
Primary
location to verify = • Outdoor PCB • IPM (Power
transistor) • Compressor
|